UL/FM Sprinkler Pipe Hangers

Purpose-made hangers for wet and dry sprinkler systems, with the double-thickness support profile and adjustable sprinkler nut that fire protection contractors in Kuwait submit against NFPA 13 specifications.

Pipe sizeDN20-2003/4" to 8" NPS
TypeType 10Sprinkler hanger
ConstructionSteelSprinkler hanger
TEMBO UL/FM listed sprinkler pipe hanger

Engineered for fire protection systems.

Sprinkler hangers support non-insulated fire fighting piping from a single shaped piece of mild steel that doubles its thickness at the support point. On the with-nut pattern (TGSHN0), the sprinkler nut rides on the hanger rod so pipe elevation can be adjusted after the hanger is up - a practical detail when levelling branch lines across a ceiling zone.

Both patterns are manufactured to MSS SP-58 Type 10 with UL listed and FM approved options, covering the hanger schedule most consultants in Kuwait review against NFPA 13 for malls, towers, hospitals, and industrial facilities.

Combined Cooperation supplies the range from DN20 (3/4") to DN200 (8") together with matching threaded rod, beam clamps, and concrete anchors, so the complete sprinkler support assembly arrives as one submittal package.

UL & FM listed
For wet & dry systems
Corrosion resistant
Design standardANSI/MSS SP-58 (Type 10)
Federal specificationWW-H-171E & A-A-1192A (Type 10)
ApprovalsUL listed / FM approved options
MaterialMild steel (other materials on request)
Maximum temperature343 C (650 F)
FinishesPlain, electro-galvanized, hot-dip galvanized, zinc flake, epoxy coated
PatternsWith sprinkler nut (TGSHN0) / without nut (TGSH00)
Hanger rod sizesM10 / M12

Sizes and dimensions

Pipe sizePipe OD (mm)Height (mm)Rod size
DN20 (3/4")26.761M10
DN25 (1")33.470M10
DN32 (1 1/4")42.178M10
DN40 (1 1/2")48.284M10
DN50 (2")60.3102M10
DN65 (2 1/2")73.0118M10
DN80 (3")88.9144M10
DN100 (4")114.3176M10
DN150 (6")168.3262M12
DN200 (8")219.1305M12

Common questions about ul/fm sprinkler pipe hangers.

01What is the difference between the TGSHN0 and TGSH00 patterns?

The TGSHN0 carries a sprinkler nut that rides on the hanger rod, so pipe elevation can still be adjusted after the hanger is up — useful when levelling branch lines across a ceiling zone. The TGSH00 is the same hanger without the nut. Both are manufactured to MSS SP-58 Type 10 with UL listed and FM approved options.

02Which rod size goes with each sprinkler hanger?

M10 rod from DN20 (3/4") up to DN100 (4"), and M12 rod for DN150 (6") and DN200 (8").

03When should a clevis hanger be used instead of a sprinkler hanger?

The sprinkler hanger range stops at DN200 and is intended for non-insulated fire fighting piping. Larger mains move to the MSS SP-58 Type 1 clevis hanger, which runs to DN750 on rod up to M30 and also carries UL listed and FM approved options.

04Can the hangers be supplied with the rest of the drop assembly?

Yes. The hangers can be supplied with matching threaded rod, beam clamps, and concrete anchors so the sprinkler support assembly goes in as one submittal. List the pipe sizes, the pattern (with or without nut), the finish, and whether the UL/FM variant is required, and a quotation follows within 24–48 hours.

Request pricing

Request a quote for ul/fm sprinkler pipe hangers.

Send the BOQ, support schedule, or consultant specification and our technical team will come back with selections, compliance notes, and indicative pricing.

Supplied onKNPC Mina Abdullah RefineryJaber Al Ahmad HospitalShuwaikh Power PlantAll 11 Kuwait references